Thursday, April 9, 2009

On-line detecting of transformer winding deformation based on parameter identification of leakage inductance

Transformers are required to demonstrate the ability to withstand short circuit currents. Over currents caused by short circuit can give rise to windings deformation. In this paper, a novel method is proposed to monitor the state of transformer windings, which is achieved through on-line detecting the leakage inductance of the windings. Specifically, the mathematical model is established for on-line identifying the leakage inductance of the windings by applying least square algorithm (LSA) to the equivalent circuit equations. The effect of measurement and model inaccuracy on the identification error is analyzed, and the corrected model is also given to decrease these adverse effect on the results. Finally, dynamic test is carried out to verify our method. The test results clearly show that our method is very accurate even under the fluctuation of load or power factor. Therefore, our method can be effectively used to on-line detect the windings deformation.
作 者:
Hao Zhiguo Zhang Baohui Li Peng
作者单位:
School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China

刊 名:
西安交通大学学报(英文版)
英文刊名:
ACADEMIC JOURNAL OF XI'AN

1 comment:

Vieena.Apple said...

参考文献
1. 金文龙.陈建华.李光范.王梦云.薛辰东 全国110kV及以上等级电力变压器短路损坏事故统计分析 [期刊论文] - 西安交通大学学报(英文版) 1999(6)
2. Zhao JX.Guo YX The diagnosis and application for winding deformation of the great transformer 2004(12)
3. Bengtsson C Status and trends in transformer monitoring 1996(3)
4. Leibfried T Monitoring of power transformers using the transfer function method 1999()
5. 姚森敬.欧阳旭东.林春耀 电力变压器绕组变形诊断分析 [期刊论文] - 西安交通大学学报(英文版) 2005(18)
6. Lech W.Tyminski L Detecting transformer winding damage:The low voltage impulse method 1966(21)
7. Humbard LE.Gillies DA Instrumentation techniques for low voltage impulse testing of power transformers 1972(3)
8. Qin SZ.Wang Y.Li YM A study of the low voltage impulse method for detecting the transformer winding deformation 1997(7)
9. Arri E.Mocci F.Tosi M On-line monitoring of electrodynamic effects on power transformers windings in Proc 1992()
10. Arri E.Mocci F.Tosi M Diagnosis of the state of power transformer windings via on-line measurement of stray reactance 1993(2)
更多...
11. 徐大可.汲胜昌.李彦明 变压器绕组变形在线监测的理论研究 [期刊论文] - 西安交通大学学报(英文版) 2000(3)
12. 高仕斌.王果 变压器绕组变形在线监测方法的改进 [期刊论文] - 西安交通大学学报(英文版) 2002(9)
13. Zhang XD Matrix Analysis and Applications 2004()
相似文献

1. 外文期刊 On-line detecting of transformer winding deformation based on parameter identification of leakage inductance

2. 外文会议 Research on Monitoring of Winding Deformation of Power Transformer by On-line Parameter Estimation about Leakage Inductance

3. 外文会议 Research on Integration of Transformer Protection and On-line Detecting Winding Deformation Based on Equivalent Circuit Equation

4. 期刊论文 漏电感参数辨识技术在线监测变压器绕组变形 - 高电压技术

5. 外文会议 Measurement of induction motor parameter identification

6. 外文会议 Accelerating performance evaluation of deep-bar induction machines from parameter identification

7. 外文会议 Estimation of saturated leakage inductances of synchronous machines using numerical field calculation and parameter identification

8. 外文会议 Estimation of saturated leakage inductances of synchronous machines using numerical field calculation and parameter identification

9. 外文会议 Online Parameter Identification Methods for Doubly Fed Induction Generators