Introduction: There are a multitude of designs, materials, formulations, and manufacturing processes that are used presently for nonceramic insulators. While this beneficial in terms of offering choices for the users, this also means that in case of problems, failure patterns could be different. It is fairly well known that most problems in NCI result originate from interfaces. The critical interfaces in this type of insulator are between the rod and housing, between hardware-rod-housing and different sheds of housing if unit is not manufactured in a single piece.
The presence of corona at the interfaces leads to sheath damage exposing the fiberglass rod, tracking the rod, thereby leading to insulator failure through interfacial flashover, rod burning and brittle fracture. Also, the presence of any contamination like water, salts, and dirt can intensify the field at those locations. Fig. 1 shows a picture of a failed NCI. It can be seen that the first few sheds have suffered corona cutting. Some degradation in the form of tracking and erosion is also visible. If the damage to the insulator is not in the line of sight, then this may not be identified as a problem during routine line inspection by road or helicopter patrols until the unit fails. The challenge is to identify such insulators at an early stage of degradation whe n there is still time to act.
Understanding the electric field distribution plays a vital role in insulator design and also can be useful for detecting internal defects. In ceramic insulators the voltage distribution is relatively more linear due to the presence of intermediate metal parts. The material does not degrade with corona, hence corona is not usually a problem in ceramic insulators. However in NCI’s the voltage distribution is highly non-uniform as shown in Fig. 2, and can give rise to corona. Corona rings are normally used for NCI at voltages above 230 kV in order to reduce the electric field near the line end.
There have been several recent publications that concluded that there is no fool-proof method for early detection of defects in nonceramic insulators. Among the methods examined were partial discharge detection, infrared thermography, corona and audible noise detection, leakage current measurement and electric field measurement. In the utility environment the electric field technique is being increasingly used as a diagnostic tool to ident ify defective porcelain units. Their use on nonceramic insulators appears to be the logical step. What types and degrees off defects can be detected by such a measurement? This study was undertaken to answer this question. The electric field distribution of a healthy insulator was taken as the reference.
Types of Defects Modeled: Several types of defects that can occur on a NCI were modeled. The various types of defects that are considered difficult to detect but critical are incorporated on to the healthy model and simulated. The size, position and conductivity of such defects are varied. The field values for locations close to the defect along the path of the probe are noted down. These values are then compared with the values obtained in the healthy cases. The presently used electric field probes are sensitive for field values above 2 kV/m. Hence defects that produce a difference of 2 kV/m and above are considered detectable while others were considered undetectable. The differences in field values thus obtained are plotted as a function of the shed number. A logarithmic trend line is fitted to the above plot for a better perception of the defect detection possibilities.
Various types of defects such as those occurring on the shed, shank, interface, external tracks from end fittings and tracks occurring on the rod sheath interface were considered. Most of the external defects could be observed during careful visual inspection. However, defects that occur inside the housing are not visible. Hence such defects are modeled for electric field distortion studies to verify the possibility of detecting such defects using field probes as shown in Table 1. A defect that occurs for the distance between any two consecutive sheds is named as the single shed defect. A single shed defect will have the shape of a cylinder with a 9.2 cm height and 5 mm diameter. A diagrammatic representation of various types of single shed defects modeled is as shown in Fig. 3. Similarly two-shed and three shed defects are simulated and analyzed.
It is likely that corona cuts or any other deformities in the insulator will give rise to corona, especially under humid conditions. The work reported last year showed that a combination of location specifics and quantitative data like brightness can provide useful information on making decisions such as problematic corona or nonproblematic corona. This should be explored further.
Conclusions:
The defect detection is position dependant and has the best possibility of being detected if it is closer to the high voltage electrode.Larger and longer defects produce higher field changes hence they are more easily detected than the smaller ones. The change in field value observed depends on the type of the defect. More conductive the defect is, greater is the possibility of detecting it. The range of the field probe can be greatly enhanced if measurements are taken radially instead of conventional axial measurements.
S. Gorur and S. Sivasubramaniyam Department of Electrical Engineering, Arizona State University, Tempe, AZ, USA
This work was performed under a PSERC funded project at Arizona State University